What Our Customers Are Saying
| Product type | Actuator |
| IP rating | IP54 |
| Manufacturer | Belimo |
| Power Supply | 230Vac, 1Ph, 50Hz |
| Torque | 2.5 Nm |
| Running time | 65 to 80 sec |
| End Switches | 1 End Switch |
| Fail Safe | Spring Return |
| Ideal for | ball valves |
Find all parts for your ventilation system at iacs, the Free Delivery and 1-2 Delivery is available for all the Belimo Actuators in stock
The Belimo TRF230-S is a type of Actuator used in HVAC and ventilation systems.
The force applied by the Torque of the TRF230-S is 2.5 Nm.
The power supply requested for this Rotary Actuator is 230Vac.
Find at IACS the ideal Belimo Actuator compatible with your system at the best price.
If you are unsure about size or installation, refer to the Belimo custom datasheet above or message iacs to receive special instructions and a custom quote.
TRF230-S - Spring-return actuator NC
• 2 Nm, 40...75 s (0...2 Nm), 95°
• AC 230 V, Open/Close, 1 x SPDT
• Running time spring 75s
• Control Open/Close with single-wire contact
• Auxiliary switch potential-free, 0...100 % adjustable
• Emergency control closedYES
Features
• Electrical Nominal voltage AC 100 ... 240 V, 50/60 Hz
• Nominal voltage range AC 85 ... 265 V
• Power consumption In operation 2.5 W @ nominal torque At rest 1.5 W For wire sizing 5 VA
• Auxiliary switch 1 x SPDT, 1 mA ... 3 (0,5) A, AC 250 V II (adjustable 0 ... 100%<) )
• Connection Motor Cable 1 m, 2 x 0.75 mm2 Auxiliary switch Cable 1 m, 3 x 0.75 mm2
• Parallel connection Yes (note performance data for supply!)
• Functional data Torque Motor Min. 2 Nm @ nominal voltage Spring-return Min. 2 Nm
• Direction of rotation see «Overview of types»
• Manual override No
• Angle of rotation Max. 95°<)
• Running time Motor <75 s (0 ... 2 Nm) Spring-return 75 s
• Sound power level Motor Max. 50 dB (A) Spring-return ~43 dB (A)
• Service life Min. 60’000 emergency settings
• Position indication Mechanical
• Safety Protection class III Safety extra-low voltage
• Degree of protection IP42 in any mounting position
• EMC CE according to 2004/108/EC Low-voltage directive CE according to 2006/95/EC
• Mode of operation Type 1 ( EN 60730-1)
• Rated impulse voltage 4 kV (to EN 60730-1)
• Control pollution degree 3 (to EN 60730-1)
• Ambient temperature –30 ... +50°C
• Media temperature +5 ... +100°C (in ball valve)
• Non-operating temperature –40 ... +80°C
• Ambient humidity range 95% r.H., non-condensating (EN 60730-1)
• Maintenance Maintenance-free
• Dimensions / Weight Dimensions See «Dimensions» on page 2
• Weight Approx. 600 g (without ball valve)