SKU
22DTH-11MN

22DTH-11MN - Belimo Duct Humidity, Temperature Sensor (L=140mm), DC 0...5 V, DC 0...10 V rH% and NTC | Belimo Sensors

£201.60 £168.00
In stock
Only 4 left
Free delivery over £30
Manuals & Datasheets

MANUAL 

 MOUNTING

INSTRUCTIONS 

 BROCHURE 
Manual DATASHEET BROCHURE
 
IP ratingIP65
Output Signal0..10Vdc
ManufacturerBelimo
Power Supply24Vac/Vdc
Sensor TypeTemperature and Humidity
Sensor characteristicsDuct Mounted
Probe Length50 mm

Explore all the components for your ventilation system at iacs. All Belimo Humidity, CO2 Air Quality and Temperature Sensors in stock are ready for free delivery or 1-2 working days delivery.

The Belimo 22DTH-11MN is a Sensor used in HVAC applications that provides precise measurements of Temperature and Humidity.

The Sensor 22DTH-11MN is a solution used for duct measurement.

Find the best-priced Belimo Sensor that is compatible with your system at iacs.

If you have questions about size or installation, consult the Belimo custom datasheet above or send an email to iacs to get personal ised guidance.

Electrical data Power Supply DC 15...24 V, ±10%, 0.4 W
  Power Supply AC 24 V, ±10%, 0.8 VA
  Electrical connection Removable spring loaded terminal block max. 2.5 mm²
  Cable entry cable gland PG11 Ø6...10 mm, with strain relief Ø6...8 mm
Functional data Sensor Technology Polymer capacitive sensor with stainless steel wire mesh filter
  Multirange YES
  Output signal active note Output DC 0...5/10 V with Jumper adjustable Voltage output: min. 10 kΩ load
  Media Air
Measuring data Measured values Temperature
    Humidity
    Dew point
    Enthalpies
    Absolute humidity
  Measuring range humidity 0...100% rH non-condensing
  Measuring range temperature  Passiv Sensor: depending on sensor type range selectable
   
Settings  range[°C]  range [°F] Factory setting
S0 -40...60 °C  -40...160 °F  
S1 0...50 °C 40...140 °F  
S2 -15...35 °C 0...100 °F  
S3 -20...80 °C 0...200 °F  
  Measuring range absolute humidity adjustable at the transducer:
    0...50 g/m³ (default setting)
    0...80 g/m³
  Measuring range enthalpy 0...85 kJ/kg
  Measuring range dew point adjustable at the transducer:
    0...50 °C (default setting)
    -20...80 °C
  Accuracy humidity ±2% between 10...90% rH @ 21 °C
  Accuracy temperature ±0.5 °C @ 25 °C
    NTC10k Pre (10k3): ±0.2 °C @ 25 °C
  Operating condition air flow max. 12 m/s
Materials Cable gland PA6, black
  Housing Cover: Lexan, Belimo orange NCS S0580- Y6OR
    Bottom: Lexan, Belimo orange NCS S0580- Y6OR
    Seal: 0467 NBR70, black
Scope of delivery Mounting flange