| Ref. |
Description |
| Main features |
Up to two circuits and 2 + 2 compressors |
| Compressors in tandem configuration with possible BLDC compressor |
| Air/water chiller or heat pump (A/W) |
| Water/water chiller or heat pump (W/W) |
| 1 evaporator per unit |
| Air-cooled condenser with separate/shared air circuit for A/W units |
| Water-cooled condenser with single circuit for W/W units |
| Hardware |
Panel mounted model: management of ON-OFF compressors |
| DIN rail mounted model: management of ON-OFF compressors |
| DIN rail mounted model, enhanced: management of ON-OFF compressors |
| DIN rail mounted model, high efficiency: management of BLDC compressors |
| User interface |
7-segment, 2-row LED display, optional pGDx graphic display, communication via APPLICA app (compatible with NFC and BTLE) for mobile devices |
| Temperature control |
PID at start-up |
| PID in operation |
| Set point compensation on outdoor temperature |
| Compressor rotation |
FIFO or timed |
| Compressor management |
Specific BLDC compressors (see list on KSA - μChiller section) |
| Generic scroll compressors |
| Oil management with BLDC |
Oil recovery function (extended operation at part load) |
| Oil equalisation (tandem with BLDC compressor) |
| Circuit destabilisation |
Forced compressor rotation (extended operation at part load) |
| ExVdriver |
Built-in valve driver on enhanced and high efficiency models |
| External driver management via FieldBus port (all versions) |
| Programming with time bands |
UnitON-OFFor2ndsetpoint(1timebandperday) |
| "Noise reduction" function for condenser fans (1 time band per day) |
| User pumps |
1/2 pumps (2 pumps only with 2 circuits) |
| Rotation by time or with pump overload alarm |
| Water-cooled condenser |
1commonpumpforbothcircuits |
| Air-cooled condenser |
Independent fans on each circuit or common to both circuits |
| Fan modulation based on condensing temperature (On/Off fan control via CAREL CONVONOFF0 module) |
| Optimised start-up to quickly bring the compressor(s) to steady operation |
| Fan anti-block protection (harsh climate) |
| Defrost |
Simultaneous |
| Separate |
| Independent |
| Defrost interval managed based on outside temperature ("sliding defrost") |
| Prevent |
Prevention of scroll compressor operating limits in relation to condensing and evaporation temperature |
| Evaporator frost prevention |
| Total management of the BLDC compressor envelope limits |
| Alarms |
Management of automatic and manual reset according to alarm severity (see the chapter on Alarms) |
| Alarm log (up to 20 events): alarm and reset date and time recorded |
| Connectivity/supervision |
RS485serialport |
| Modbus RTU |
| Baud rate up to 115200 bit/s |
| Frame configurable by Parity (None, Even, Odd) and StopBits (1 or 2); Databits fixed at 8 bits. |