SKU
QFM81.2

QFM81.2 - Siemens Duct hygrostat, setpoint setting range 15...95 % r.h.

£173.99 £144.99
On request
Next Supplier Stock Update: 18/04/2026
Free delivery over £30
Manuals & Datasheets
 DATA-SHEET 
DATASHEET
 
Product typeSensors & Stats
IP ratingIP30
Output Signal0..10Vdc
ManufacturerSiemens
Power Supply24Vac or 24Vdc/48Vac, 50Hz
Sensor TypeHumidity
Sensor characteristicsDuct Mounted
Probe Length150 mm
Type Reference Setpoint range (Wh) Switching differential (Xd) Degree of protection Setpoint adjustment
QFM81.2 15…95 % r.h approx. 4 % r.h. IP 30 externally

Duct Hygrostats QFM81… for relative humidity

On/off hygrostat with microswitch,

with temperature-compensated humidity sensor for temperature-independent humidity measurements,

with stabilized sensing strip (good linearity, very stable even at high humidity, insensitive to dust and contaminated air),

for the control of humidification equipment,

for the control of dehumidification equipment,

for mounting in ventilating ducts or rooms

Use

The duct hygrostats are designed for controlling and monitoring the relative humidity in ventilating and air conditioning plants.

They control the humidity content of the air within an adjustable range of 15 to 95 % r.h.

In air conditioning plants with humidification, the duct hygrostat can also be used as a maximum limiter in the supply air duct.