SKU
NVKC24A-MP-RE

NVKC24A-MP-RE SuperCap Globe Valve Actuator Retrofit, AC/DC 24 V, 35 s - Belimo | ideal for globe valves

£727.44 £606.20
On request
Next Supplier Stock Update: 18/04/2026
Free delivery over £30
Manuals & Datasheets
 DATASHEET 
DATASHEET
 
Product typeActuator
IP ratingIP54
Input Signal0..10 Vdc, MP-BUS
ManufacturerBelimo
Power Supply24Vac/Vdc
Torque1000 N
Running time30 to 45 sec
Ideal for globe valves

For all of the Belimo Actuators that are in stock at iacs, we offer Free Delivery and Next 1-2 Day Delivery.

The Belimo NVKC24A-MP-REis a type of Actuator used to open valves in HVAC systems and applications.

The Torque used by the NVKC24A-MP-RE is 1000 N.

This Belimo Actuator requests a power supply of 24Vac/Vdc.

This Belimo component can be used with Globe Valves.

Find the appropriate Belimo Actuator for your system at the greatest price at iacs.

If you have questions about size or installation, consult the Belimo custom datasheet above or send an email to iacs to get personalised guidance.

NVKC24A-MP-RE SuperCap Globe Valve Actuator Retrofit, AC/DC 24 V, 35 s SuperCap globe valve actuator retrofit 1000 N, 20 mm AC/DC 24 V, modulating, MP-Bus Operating range DC 2...10 V, adjustable Position feedback DC 2...10 V, adjustable Actuating time motor 35 s / 20 mm IP 54, Manual override temporary Universal valve adapter separately Connection terminal without cable Stroke direction / closing point selectable (top/bottom) Power-Off-Position adjustable

Pre-charging time (start up): The capacitor actuators require a pre-charging time. This time is used for charging the capacitors up to a usable voltage level. This ensures that, in the event of an electricity interruption, the actuator can move at any time from its current position into the preset emergency setting position (POP). The duration of the pre-charging time depends mainly on following factors: – Duration of the electricity interruption – PF delay time (bridging time)

Delivery condition (capacitors): The actuator is completely discharged after delivery from the factory, which is why the actuator requires approximately 20 s pre-charging time before initial commissioning in order to bring the capacitors up to the required voltage level.

Converter for sensors: Connection option for a sensor (passive or active sensor or switching contact). The MP actuator serves as an analogue/digital converter for the transmission of the sensor signal via MP-Bus to the higher level system.

Parameterisable actuators: The factory settings cover the most common applications. Input and output signals and other parameters can be altered with the PC-Tool MFT-P or with the Service tool ZTH EU.

Installation on third-party valves: The retrofit actuators for installation on a wide range of valves from various manufacturers are comprised of an actuator, bracket, universal valve neck adapter and universal valve stem adapter. Adapt the valve neck and valve stem to begin with, then attach the retrofit bracket to the valve neck adapter. Now fit the retrofit actuator into the bracket and connect it to the valve. Whilst taking the position of the valve closing point into account, secure the actuator to the bracket and then conduct the commissioning process. The valve neck adapter/actuator can be rotated through 360° on the valve neck, provided it is permitted by the size of the installed valve.

Installation on BELIMO valves: Please use standard actuators from Belimo for installation on Belimo globe valves. The installation of retrofit actuators on Belimo globe valves is technically possible.

Manual override: Manual control with push-button possible - temporary. The gear is disengaged and the actuator decoupled for as long as the button is pressed. The stroke can be adjusted by using a hexagon socket screw key (4 mm), which is inserted into the top of the actuator. The stroke spindle extends when the key is rotated clockwise.

High functional reliability: The actuator is overload protected, requires no limit switches and automatically stops when the end stop is reached.

Position indication: The stroke is indicated mechanically on the bracket with tabs. The stroke range adjusts itself automatically during operation.

Home position: Factory setting: Actuator spindle is retracted. The first time the supply voltage is switched on, i.e. at the time of commissioning, the actuator carries out an adaption, which is when the operating range and position feedback adjust themselves to the mechanical setting range. The actuator then moves into the position defined by the positioning signal.

Direction of stroke: switch When actuated, the direction of stroke switch changes the running direction in normal operation. The direction of stroke switch has no influence on the emergency setting position (POP) which has been set.

Adaption and synchronisation: An adaption can be triggered manually by pressing the „Adaption“ button or with the PC-Tool. Both mechanical end stops are detected during the adaption (entire setting range). Automatic synchronisation after pressing the gearbox disengagement button is configured. The synchronisation is in the home position (0%). The actuator then moves into the position defined by the positioning signal. A range of settings can be adapted using the PC-Tool (see MFT-P documentation)

Rotary knob emergency setting position: The «Emergency setting position» rotary knob can be used to adjust the desired emergency setting position (POP). In the event of an electricity interruption, the actuator will move into the selected emergency setting position, taking into account the bridging time (PF) of 2 s which was set ex-works. Settings: The rotary knob must be set to the «Tool» position for retroactive settings of the emergency setting position with the BELIMO service tool MFT-P. Once the rotary knob is set back to the range 0…100%, the manually set value will have positioning authority

Bridging time (PF): Electricity interruptions can be bridged up to a maximum of 10 s. In the event of an electricity interruption, the actuator will remain stationary in accordance with the set bridging time. If the electricity interruption is greater than the set bridging time, then the actuator will move into the selected emergency setting position (POP). The bridging time set ex-works is 2 s. This can be modified on site in operation with the use of the BELIMO service tool MFT-P. Settings: The rotary knob must not be set to the «Tool» position! Only the values need to be entered for retroactive adjustments of the bridging time with the BELIMO service tool MFT-P.

Electrical data:

Nominal voltage AC/DC 24 V
Nominal voltage frequency 50/60 Hz
Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V
Power consumption in operation 4.5 W
Power consumption in rest position 1.5 W
Power consumption for wire sizing 9 VA
Connection supply / control Terminals 4 mm² (cable Ø 4...10 mm)
Parallel operation Yes (note the performance data)

Functional data::

Actuating force 1000 N
Positioning signal Y DC 0...10 V
Positioning signal Y note Input impedance 100 kΩ
Control signal Y variable Open-close, 3-point (AC only) and Modulating (DC 0...32 V)
Operating range Y DC 2...10 V
Operating range Y variable Start point DC 0.5...30 V and End point DC 2.5...32 V
Position feedback U DC 2...10 V
Position feedback U note Max. 0.5 mA
Position feedback U variable Start point DC 0.5...8 V and End point DC 2.5...10 V
Setting emergency position (POP) Actuator spindle 0...100%, adjustable (POP rotary button)
Bridging time (PF) variable 1...10 s
Position accuracy 5% absolute
Manual override Gear disengagement with push-button
Nominal stroke 20 mm
Actuating time 35 s / 20 mm
Actuating time variable 35...90 s / 20 mm
Actuating time emergency control function 35 s / 20 mm
Adaption setting range variable No action, adaption when switched on Adaption after pushing the gear disengagement button
Override control MAX (maximum position) = 100%, MIN (minimum position) = 0% and ZS (intermediate position, AC only) = 50%
Override control variable MAX = (MIN + 33%)...100%, MIN = 0%...(MAX – 33%) and ZS = MIN...MAX
Sound power level motor 60 dB(A)
Sound power level emergency control position 60 dB(A)
Position indication Mechanically, 5...20 mm stroke

Safety:

Protection class IEC/EN III Safety extra-low voltage
Degree of protection IEC/EN IP54
EMC CE according to 2004/108/EC
Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14
Mode of operation Type 1.AA
Rated impulse voltage supply / control 0.8 kV
Control pollution degree 3
Ambient temperature 0...50°C
Non-operating temperature -40...80°C
Ambient humidity 95% r.h., non-condensing
Maintenance Maintenance-free

Weight: Approx. 2.8 kg

Terms Abbreviations: POP = Power off position / emergency setting position, CPO = Controlled power off / controlled emergency control function, PF = Power fail delay time / bridging time