What Our Customers Are Saying
| Product type | Actuator |
| IP rating | IP54 |
| Input Signal | On/Off |
| Manufacturer | Belimo |
| Power Supply | 24Vac/Vdc |
| Torque | 40 Nm |
| Running time | 140 to 150 sec |
| Actuator type | Rotary |
Find all the components for your ventilation system at IACS. All Belimo Actuators on hand are eligible for Free Delivery and 1-2 Delivery.
The Belimo GK24G-1 is a kind of Actuator used to manage dampers in HVAC applications and systems.
To control the damper, this kind of Actuator turns it by Rotary motion.
The Torque used by the GK24G-1 is 40 Nm.
This Belimo Actuator requests a power supply of 24Vac/Vdc.
Find at IACS the ideal Belimo Actuator compatible with your system at the best price.
If you are unsure about size or installation, refer to the Belimo custom datasheet above or message iacs to receive special instructions and a custom quote.
GM230A -Damper actuator 40 Nm, 150 s, 95° AC 230 V, Open/Close
• IP 54, Manual override with push-button
• Control with 2-wire or single-wire contact
• Connection PVC cable 1m
• Direction of rotation reversible (right/left)
• Angle of rotation limit. mechanical integral
• Spindle driver universal spindle clamp
Features
• Electrical data Nominal voltage AC 100 ... 240 V, 50/60 Hz
• Nominal voltage range AC 85 ... 265 V
• Power consumption In operation 5 W @ nominal torque
• At rest 2 W
• For wire sizing 9 VA
• Connection Cable Cable 1 m, 3 x 0.75 mm2
• Functional data Torque (nominal torque) Min. 40 Nm @ nominal voltage
• Direction of rotation Reversible with switch 0 anticlockwise and 1 clockwise
• Manual override Gearing latch disengaged with push-button, can be locked
• Angle of rotation Max. 95° , limited on both sides by means of adjustable, mechanical end stops
• Running time 150 s / 90°
• Sound power level Max. 45 dB (A)
• Position indication Mechanical, pluggable
• Safety Protection class II Totally insulated
• Degree of protection IP54 in any mounting position NEMA2, UL Enclosure Type 2
• EMC CE according to 2004/108/EC
• Low-voltage directive CE according to 2006/95/EC
• Mode of operation Type 1 (EN 60730-1)
• Rated impulse voltage 2.5 kV (EN 60730-1)
• Control pollution degree 3 (EN 60730-1)
• Ambient temperature –30 ... +50°C
• Non-operating temperature –40 ... +80°C
• Ambient humidity 95% r.H., non-condensating (EN 60730-1)
• Maintenance Maintenance-free
• Dimensions / Weight Dimensions See «Dimensions» on page 2
• Weight Approx. 1700 kg