| Product type | Actuator |
| IP rating | IP54 |
| Input Signal | On/Off |
| Manufacturer | Belimo |
| Power Supply | 24Vac/Vdc |
| Torque | 2 Nm |
| Running time | 65 to 80 sec |
| Actuator type | Rotary |
Find all the components for your ventilation system at IACS. All Belimo Actuators on hand are eligible for Free Delivery and 1-2 Delivery.
The Belimo CM24-T-R is a kind of Actuator used to manage dampers in HVAC applications and systems.
To control the damper, this kind of Actuator turns it by Rotary motion.
The Torque used by the CM24-T-R is 2 Nm.
This Belimo Actuator requests a power supply of 24Vac/Vdc.
IACS has the best prices on the right Belimo Actuators for your system.
Consult the Belimo custom datasheet above or contact iacs via email for personalised assistance if you have queries about size or installation.
CM24-T-R Damper actuator 2 Nm, 75 s / 95°, 0...287.5° AC / DC 24 V, Open/Close
• Damper actuator
• 2 Nm, 75 s,
• AC / DC 24 V, Open/Close, 3-point
• IP 54, Manual override Gear disengagement with magnet
• Control with single- / 2-wire contact
• Connection PVC cable 1m
• Direction of rotation rotation to the right (cw)
• Running direction rotation to the right - cw
• Angle of rotation limit. mechanical integral
• Spindle driver Clamp 6...12.7 mm
• Nominal voltage AC 24 V, 50/60 Hz / DC 24 V
• Nominal voltage range AC/DC 19.2 ... 28.8 V
• Power consumption In operation At rest For wire sizing 0.5 W @ nominal torque 0.2 W 1 VA
• Connection Terminals for 3 x 1.5 mm2 CU wire or 3 x 1.0 mm2 CU litz wires
• Functional data Torque (nominal torque) Min. 2 Nm @ nominal voltage
• Direction of rotation See «Type overview»
• Angle of rotation Without limit With limit Endless Fixed 315° or 0 ... 287.5° with mechanical end stops, can be adjusted in 2.5° increments
• Running time 75 s / 90°
• Sound power level Max. 35 dB (A)
• Position indicator Mechanical, pluggable (with integrated magnet for gear disengagement)
• Safety Protection class III Safety extra-low voltage / UL Class 2 Supply
• Degree of protection IP20 in any mounting position NEMA1, UL Enclosure Type 1
• EMC CE according to 2004/108/EC
• Certification cULus according to UL 60730-1A and UL 60730-2-14 and CAN/CSA E60730-1:02 Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
• Mode of operation Type 1 (EN 60730-1)
• Rated impulse voltage 0.8 kV (EN 60730-1)
• Control pollution degree 2 (EN 60730-1)
• Ambient temperature –30 ... +50°C
• Non-operating temperature –40 ... +80°C
• Ambient humidity 95% r.H., non-condensating (EN 60730-1)
• Maintenance – free