 DATA-SHEET 
DATASHEET
 
Product typeActuator
IP ratingIP54
Input SignalOn/Off
ManufacturerBelimo
Power Supply230Vac, 1Ph, 50Hz
Torque2 Nm
Running time65 to 80 sec
Actuator typeRotary

Find all the components for your ventilation system at IACS. All Belimo Actuators on hand are eligible for Free Delivery and 1-2 Delivery.

The Belimo CM230-R is a kind of Actuator used to manage dampers in HVAC applications and systems.

To control the damper, this kind of Actuator turns it by Rotary motion.

The Torque used by the CM230-R is 2 Nm.

This Belimo Actuator requests a power supply of 230Vac.

IACS has the best prices on the right Belimo Actuators for your system.

Consult the Belimo custom datasheet above or contact iacs via email for personalised assistance if you have queries about size or installation.

CM230-R Damper actuator 2 Nm, 75 s / 90°, AC 230 V, Open/Close

•    Damper actuator
•    2 Nm, 75 s,
•    AC 230 V, Open/Close, 3-point
•    IP 54, Manual override Gear disengagement with magnet
•    Control with single- / 2-wire contact
•    Connection PVC cable 1m
•    Direction of rotation rotation to the right (cw)
•    Angle of rotation limit. mechanical integral

Features

  • Simple direct mounting on the damper spindle with a universal spindle clamp (6 ... 12.7 mm). The actuator is then secured with the anti-rotation strap supplied, to prevent it from rotating.

  • Manual override with magnet possible (the gear is disengaged as long as the magnet adheres to the symbol U). The magnet for gear disengagement is integrated in the position indicator.

  • Adjustable angle of rotation with mechanical end stops.

  • High functional reliability The actuator is overload-proof, requires no limit switches and automatically stops when the end stop is reached.

•    Nominal voltage AC 100 ... 240 V, 50/60 Hz
•    Nominal voltage range AC 85 ... 265 V
•    Power consumption In operation At rest For wire sizing    1.5 W @ nominal torque 1 W 3 VA
•    Connection Cable 1 m, 3 x 0.75 mm2
•    Functional data    Torque (nominal torque) Min. 2 Nm @ nominal voltage
•    Direction of rotation See «Type overview»
•    Manual override Gear disengagement with magnet
•    Angle of rotation Without limit With limit Endless Fixed 315° or 0 ... 287.5° with mechanical end stops, can be adjusted in 2.5° increments
•    Running time 75 s / 90°
•    Sound power level Max. 35 dB (A)
•    Position indicator Mechanical, pluggable (with integrated magnet for gear disengagement)
•    Safety    Protection class II totally insulated
•    Degree of protection IP54 in any mounting position NEMA2, UL Enclosure Type 2
•    EMC Low voltage directive CE according to 2004/108/EC CE according to 2006/95/EC
•    Certification cULus according to UL 60730-1A and UL 60730-2-14 and CAN/CSA E60730-1:02 Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
•    Mode of operation Type 1 (EN 60730-1)
•    Rated impulse voltage 2.5 kV (EN 60730-1)
•    Control pollution degree 3 (EN 60730-1)
•    Ambient temperature –30 ... +50°C
•    Non-operating temperature –40 ... +80°C
•    Ambient humidity 95% r.H., non-conde
•    Maintenance – free