SKU
22UTH-110X

22UTH-110X - Belimo Outside Humidity, Temperature Sensor, DC 0...5 V, DC 0...10 V

£299.04 £249.20
On request
Next Supplier Stock Update: 18/04/2026
Free delivery over £30
Manuals & Datasheets

MANUAL 

 MOUNTING

INSTRUCTIONS 

 BROCHURE 
Manual DATASHEET BROCHURE
 
IP ratingIP65
Output Signal0..10Vdc
ManufacturerBelimo
Power Supply24Vac/Vdc
Sensor TypeTemperature and Humidity
Sensor characteristicsOutdoor
Probe Length140 mm

Visit iacs to find every part of your HVAC system. In stock Belimo Humidity, CO2 Air Quality and Temperature Sensors may all be delivered with free delivery or 1-2 working days delivery.

The Belimo 22UTH-110X is a Sensor that offers accurate measurements of Temperature and Humidity and is utilised in HVAC applications.

This type of Belimo Sensor 22UTH-110X is a solution used to measure values of outdoor environments.

Find the best-priced Belimo Sensor that is compatible with your system at iacs.

If you have questions about size or installation, consult the Belimo custom datasheet above or send an email to iacs to get personal ised guidance.

Electrical data Power Supply DC 15...24 V, ±10%, 0.4 W
  Power Supply AC 24 V, ±10%, 0.8 VA
  Electrical connection Removable spring loaded terminal block max. 2.5 mm²
  Cable entry cable gland PG11 Ø6...10 mm, with strain relief Ø6...8 mm
Functional data  Multirange YES
  Output signal active note Output DC 0...5/10 V with Jumper adjustable Voltage output: min. 10 kΩ load
  Media Air
Measuring data Measured values Temperature
    Humidity
    Dew point
    Enthalpies
    Absolute humidity
  Measuring range humidity 0...100% rH non-condensing
  Measuring range temperature range selectable
   
Settings  range[°C] range [°F] Factory setting
S0 -40...60 °C  -40...160 °F  
S1 0...50 °C  40...140 °F  
S2 -15...35 °C   0...100 °F  
S3 -20...80 °C   0...200 °F            X
  Measuring range absolute humidity  adjustable at the transducer:
    0...50 g/m³ (default setting)
    0...80 g/m³
  Measuring range enthalpy 0...85 kJ/kg
  Measuring range dew point adjustable at the transducer:
    0...50 °C (default setting)
    -20...80 °C
  Accuracy humidity ±2% between 10...90% rH @ 21 °C
  Accuracy temperature ±0.5 °C @ 25 °C
  Operating condition air flow max. 12 m/s
Materials Cable gland PA6, white
  Housing Cover: Lexan, white
    Bottom: Lexan, white
    Seal: 0467 NBR70, black
Scope of delivery Dowel  
  Screws