What Our Customers Are Saying
| Product type | Actuator |
| IP rating | IP54 |
| Input Signal | 0..10 Vdc |
| Manufacturer | Belimo |
| Power Supply | 24Vac/Vdc |
| Torque | 20 Nm |
| Running time | 90 to 105 sec |
| Actuator type | Rotary |
| Ideal for | butterfly valves, rotary valves |
Find all parts for your ventilation system at iacs, the Free Delivery and 1-2 Delivery is available for all the Belimo Actuators in stock
The Belimo SR24A-SR-TP is a type of Actuator used in HVAC and ventilation systems.
This kind of Actuator rotates the damper in order to control it.
The force applied by the Torque of the SR24A-SR-TP is 20 Nm.
This Rotary Actuator needs to be supported by a power supply of 24Vac/Vdc.
Find at IACS the ideal Belimo Actuator compatible with your system at the best price.
If you are unsure about size or installation, refer to the Belimo custom datasheet above or message iacs to receive special instructions and a custom quote.
• AC 24 V, modulating
• Running time motor 90 s / 90°
• Operating range DC 2...10 V
• Position feedback DC 2...10 V
• IP 54, Manual override temporary, permanent
• Connection PVC cable 1mt
• Operating range DC 2...10 V
• Position feedback DC 2...10 V
• Position indicator mechanical
• Terminal connections
Features
• Electrical data Nominal voltage AC 24 V, 50/60 Hz DC 24 V
• Power supply range AC/DC 19.2 ... 28.8 V
• Power consumption In operation 2 W @ nominal torque At rest 0.2 W Dimensioning 4 VA
• Connection Cable 1 m, 4 x 0.75 mm2
• Parallel connection Possible, note performance data
• Functional data Torque Motor Min. 20 Nm @ nominal voltage
• Control Control Signal Y DC 0 ... 10 V, typical input impedance 100kΩ Operating range DC 2 ... 10 V
• Position feedback DC 2 ... 10 V, max. 1 mA (Measuring voltage U)
• Position accuracy ±5%
• Manual override Gearing latch disengaged with pushbutton (temporary-permanent)
• Running time ≤90 s / 90°<)
• Noise level Max. 45 dB (A) (without the valve)
• Position indication Mechanical, integral
• Safety Protection class III Extra low voltage
• Degree of protection IP54 in any mounting position
• EMC CE according to 89/336/EEC
• Mode of operation Type 1 (to EN 60730-1)
• Rated impulse voltage 0.8 kV (to EN 60730-1)
• Control pollution degree 3 (to EN 60730-1)
• Ambient temperature 0 ... +50°C
• Media temperature +5 ... +100°C in (control) ball valve –10°C with stem heating upon request
• Non-operating temperature –40 ... +80°C
• Ambient humidity 95% r.h., non-condensating
• Maintenance Maintenance-free
• Dimensions / Weight Dimensions See «Dimensions» on page 2