 DATA-SHEET 
DATASHEET
 
Product typeActuator
IP ratingIP54
Input SignalOn/Off
ManufacturerBelimo
Power Supply24Vac/Vdc
Torque450 N
Running time140 to 150 sec
Actuator typeLinear

Find all the components for your ventilation system at IACS. All Belimo Actuators on hand are eligible for Free Delivery and 1-2 Delivery.

The Belimo SH24A200 is a kind of Actuator used in HVAC applications and air ventilation systems.

The Torque used by the SH24A200 is 450 N.

This Belimo Actuator requests a power supply of 24Vac/Vdc.

Find the appropriate Belimo Actuator for your system at the greatest price at iacs.

If you have questions about size or installation, consult the Belimo custom datasheet above or send an email to iacs to get personalised guidance.

SH24A200  - Linear actuator with rack

•    450 N, 150 s / 100 mm / constant, 
•    AC 230 V, Open/Close, 3-point
•    Stroke range 0...200 mm
•    IP 54, Manual override by means of push-button
•    Control with single- / 2-wire contact
•    Connection PVC cable 1m


Features
 

  • Manual override Manual override with push-button possible (the gear is disengaged for as long as the button is pressed or remains locked).

  • Adjustable stroke The stroke of the gear rack can be adjusted on both sides in increments of 20 mm by means of mechanical end stops.

  • High functional reliability The actuator is overload-proof, requires no limit switches and automatically stops when the end stop is reached.


•     Electrical data Nominal voltage AC 100 ... 240 V, 50/60 Hz
•     Power supply range AC 85 ... 265 V 
•     Power consumption In operation 2.5 W @ nominal force At rest 0.6 W For wire sizing 6 VA
•     Connection Cable 1 m, 3 x 0.75 mm2
•     Functional data Actuating force 450 N @ nominal voltage
•     Stroke See «Overview of types»
•     Direction of stroke Reversible with switch 1 resp. 0
•     Running time 150 s / 100 mm
•     Sound power level <50 dB (A)
•     Safety Protection class II totally insulated
•     Degree of protection IP54 in any mounting position NEMA 2, UL Enclosure Type 2
•     EMC CE according to 2004/108/EC Low-voltage directive CE according to 2006/95/EC
•     Certification cULus according to UL 60730-1A and UL 60730-2-14 and CAN/CSA E60730-1:02 Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
•     Mode of operation Type 1
•     Rated impulse voltage 4 kV
•     Control pollution degree 3
•     Ambient temperature range –30 ... +50°C
•     Non-operating temperature –40 ... +80°C
•     Ambient humidity range 95% r.H., non-condensating
•     Maintenance Maintenance-free
•     Dimensions / Weight Dimensions See «Dimensions» on page 3
•     Weight See «Overview of types»