What Our Customers Are Saying
| Product type | Actuator |
| IP rating | IP54 |
| Input Signal | On/Off |
| Manufacturer | Belimo |
| Torque | 20 Nm |
| Running time | 65 to 80 sec |
| Actuator type | Rotary |
| Fail Safe | Spring Return |
Find all the components for your ventilation system at IACS. All Belimo Actuators on hand are eligible for Free Delivery and 1-2 Delivery.
The Belimo SFG-L is a kind of Actuator used in HVAC applications and air ventilation systems.
The Torque used by the SFG-L is 20 Nm.
The power supply requested for this Rotary Actuator is AC 24...240 V / DC 24...125 V.
Find at IACS the ideal Belimo Actuator compatible with your system at the best price.
If you are unsure about size or installation, refer to the Belimo custom datasheet above or message iacs to receive special instructions and a custom quote.
SFG-L - Spring-return actuator 20 Nm, 75 s / 95°, 95°
• AC (DC) 24...230 V, Open/Close
• IP 66 NEMA4, Manual override with integrated position stop
• Running time spring < 20 s / ccw
• Connection cable FRNC 1 m
• Spindle driver universal spindle clamp
• Angle of rotation limit. mech. adjustable
Features
• Electrical data Nominal voltage AC 24 ... 240 V, 50/60 Hz / DC 24 ... 125 V
• Nominal voltage range AC 19,2 ... 264 V / DC 21,6 ... 137.5 V
• Power consumption In operation 7 W @ nominal torque At rest 3.5 W For wire sizing 18 VA
• Connection Motor Cable 1 m, 2 x 0.75 mm2
• Functional data Torque Motor Min. 20 Nm @ nominal voltage Spring return Min. 20 Nm
• Direction of rotation Spring return L (ccw)
• Manual override With hand crank and interlocking switch
• Angle of rotation Max. 95°<), can be limited with adjustable mechanical end stop
• Running time Motor ≤150 s / 90°<) Spring return ≤20 s @ –20 ... 50°C / max. 60 s @ –30°C
• Sound power level Motor ≤45 dB (A) Spring return ≤62 dB (A)
• Service life Min. 60,000 emergency positions
• Position indication Mechanica
• Safety Protection class II Totally insulated
• Protection mode IP66 NEMA2, UL Enclosure Type 4
• EMC CE according to 2004/108/EC Low-voltage directive CE according to 2006/95/EC
• Certification Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14cULus according to UL 60730-1 and UL 60730-2-14and CAN/CSA E60730-1:02
• Mode of operation Type 1.AA
• Rated impulse voltage 4 kV
• Control pollution degree 4
• Ambient temperature –30 ... +50°C
• Non-operating temperature –40 ... +80°C
• Ambient humidity 100% r.h., non-condensating
• Maintenance Maintenance-free
• Dimensions / Weight Dimensions See «Dimensions» on page 3
• Weight Approx. 5.2 kg