What Our Customers Are Saying
| Product type | Actuator |
| IP rating | IP54 |
| Input Signal | On/Off |
| Manufacturer | Belimo |
| Power Supply | 230Vac, 1Ph, 50Hz |
| Torque | 10 Nm |
| Running time | 90 to 105 sec |
| End Switches | 1 End Switch |
| Actuator type | Rotary |
| Ideal for | ball valves |
Find all the components for your ventilation system at IACS. All Belimo Actuators on hand are eligible for Free Delivery and 1-2 Delivery.
The Belimo NR230A-S is a kind of Actuator used in HVAC applications and air ventilation systems.
To control the damper, this kind of Actuator turns it by Rotary motion.
The Torque used by the NR230A-S is 10 Nm.
This Belimo Actuator requests a power supply of 230Vac.
Find at IACS the ideal Belimo Actuator compatible with your system at the best price.
If you are unsure about size or installation, refer to the Belimo custom datasheet above or message iacs to receive special instructions and a custom quote.
NR230A-S - Rotary actuator for control BV 10 Nm
• AC 230 V, Open/Close, 3-point, 1 x SPDT
• Running time motor 90 s / 90°
• IP 54, Manual override temporary, permanent
• Connection cable length = 1 m
• Position indicator mechanical
Features
• Electrical data Nominal voltage AC 100 ... 240 V, 50/60 Hz
• Nominal voltage range AC 85 ... 265 V
• Power consumption In operation 2.5 W @ nominal torque
• At rest 0.6 W
• For wire sizing 5.5 VA
• Auxiliary switch1 x SPDT, 1 mA ... 3 (0.5) A, AC 250 V II(0 ... 100% adjustable)
• Connection Motor Cable 1 m, 3 x 0.75 mm2 Auxiliary switch Cable 1 m, 3 x 0.75 mm2
• Parallel connectionPossible, note performance data
• Functional dataTorque (nominal torque)Min. 10 Nm @ nominal voltage
• Manual overrideGearing latch disengaged with pushbutton, can be locked
• Running time150 s / 90°<
• Sound power levelMax. 35 dB (A) (without the valve)
• Position indication Mechanical, pluggable
• Safety Protection classII totally insulated
• Degree of protectionIP54 in any mounting position NEMA 2, UL Enclosure Type 2
• EMC CE according to 2004/108/EC Low-voltage directive CE according to 2006/95/EC
• Certification cULus according to UL 60730-1A and UL 60730-2-14and CAN/CSA E60730-1:02Certified to IEC/EN 60730-1 and IEC/EN 60730-2-14
• Mode of operationType 1
• Rated impulse voltage 2.5 kV
• Control Pollution Degree3
• Ambient temperature range–0 ... +50°C
• Media temperature +5 ... +110°C in (control) ball valve–10°C with stem heating upon request
• Non-operating temperature–40 ... +80°C
• Maintenance Maintenance-free
• Dimensions / WeightDimensionsSee «Dimensions» on page3
• WeightApprox. 800 g