What Our Customers Are Saying
| Product type | Actuator |
| IP rating | IP54 |
| Input Signal | 0..10 Vdc |
| Manufacturer | Belimo |
| Power Supply | 24Vac/Vdc |
| Torque | 10 Nm |
| Running time | 140 to 150 sec |
| Actuator type | Rotary |
| Fail Safe | Spring Return |
Find all parts for your ventilation system at iacs, the Free Delivery and 1-2 Delivery is available for all the Belimo Actuators in stock
The Belimo NF24G-SR-L is a type of Actuator used in HVAC and ventilation systems.
The force applied by the Torque of the NF24G-SR-L is 10 Nm.
The power supply requested for this Rotary Actuator is 24Vac/Vdc.
Find at IACS the ideal Belimo Actuator compatible with your system at the best price.
If you are unsure about size or installation, refer to the Belimo custom datasheet above or message iacs to receive special instructions and a custom quote.
NF24G-SR-L - Spring-return actuator 10 Nm, < 150 s / 90°, 90°
• AC / DC 24 V, modulating
• IP 66 NEMA4, Manual override with integrated position stop
• Running time spring < 20 s / ccw
• Control DC 0...10 V
• Operating range DC 2...10 V
• Position feedback DC 2...10 V
• Connection cable FRNC 1 m
• Spindle driver universal spindle clamp
• Angle of rotation limit. mech. adjustable
Features
• Electrical data Nominal voltage AC 24 V, 50/60 Hz DC 24 V
• Nominal voltage range AC 19.2 ... 28.8 V / DC 21.6 ... 28.8 V
• Power consumption In operation 3.5 W @ nominal torque At rest 2.5 W For wire sizing 5.5 VA(lmax 20 A @ 5 ms)
• ConnectionCable 1 m, 4 x 0.75 mm2
• Functional data Torque Motor Min. 10 Nm @ nominal voltage Spring return Min. 10 Nm
• ControlControl signal YDC 0 … 10 V, input impedance 100 k Operating range DC 2 … 10 V
• Position feedback (measuring voltage U)DC 0.5 … 10 V, max. 0.5 mA
• Position accuracy±5%
• Direction of rotation Motor Reversible with switch Spring return /L (ccw)
• Manual overrideWith hand crank and interlocking switch
• Angle of rotationMax. 95°<, can be limited with adjustable mechanical end stop
• Running time Motor ≤150 s (0 ... 10 Nm) Spring return ≤20 s @ –20 ... 50°C / max. 60 s @ –30°C
• Sound power levelMotor≤40 dB (A) @ 150 s running time Spring return ≤62 dB (A)
• Service lifeMin. 60,000 emergency positions
• Position indicationMechanical
• Safety
• Protection classIII Safety extra-low voltageUL Class 2 Supply
• Degree of protectionIP66NEMA 4, UL Enclosure Type 4
• EMC CE according to 2004/108/EC
• Safety
• CertificationCertified to IEC/EN 60730-1 and IEC/EN 60730-2-14cULus according to UL 60730-1 and UL 60730-2-14A and CAN/CSA E60730-1:02
• Mode of operationType 1.AA
• Rated impulse voltage0.8 kV
• Control pollution degree 4
• Ambient temperature –30 ... +50°C
• Non-operating temperature –40 ... +80°C
• Ambient humidity100% r.h.
• Maintenance Maintenance-free
• Dimensions / Weight Dimensions See «Dimensions» on page 3
• Weight Approx. 4.8 kg