What Our Customers Are Saying
| Product type | Actuator |
| IP rating | IP54 |
| Input Signal | 0..10 Vdc |
| Manufacturer | Belimo |
| Power Supply | 230Vac, 1Ph, 50Hz |
| Torque | 5 Nm |
| Running time | 140 to 150 sec |
| Actuator type | Rotary |
| Control Type | Modulating |
At IACS we provide Free Delivery and Next 1-2 day Delivery for all the Belimo Actuators in stock.
The Belimo LM230ASR-TP is an Actuator used in HVAC systems and applications to manage dampers.
This type of Actuator applies a Rotary motion to regulate the damper.
The Torque force applied by the LM230ASR-TP is 5 Nm.
The power supply requested for this Rotary Actuator is 230Vac.
IACS has the best prices on the right Belimo Actuators for your system.
Consult the Belimo custom datasheet above or contact iacs via email for personalised assistance if you have queries about size or installation.
Features
• Electrical data Nominal voltage AC 100 ... 240 V, 50/60 Hz
• Nominal voltage range AC 85 ... 265 V
• Power consumption In operation 1.8 W @ nominal torque
• At rest 1 W
• For wire sizing 4 VA
• Connection Power supply Signals
• Terminals 4 mm2 (Cable Ø 6 ... 8 mm, two-core)
• Terminals 4 mm2 (Cable Ø 6 ... 8 mm, four-core)v
• Functional data Torque (nominal torque) Min. 5 Nm @ nominal voltage
• Control Control signal Y DC 0 ... 10 V, typical input impedance 100 kΩ
• Working range DC 2 ... 10 V
• Position feedback (Measuring voltage) DC 2 ... 10 V, max. 1 mA
• Auxiliary supply DC 24 V ±30%, max. 10 mA
• Position accuracy ±5%
• Direction of rotation Reversible with switch
• Direction of rotation at Y = 0 V At switch position resp.
• Manual override Gearing latch disengaged with pushbutton, detentable
• Angle of rotation Max. 95° , limited on both sides by means of adjustable, mechanical end stops
• Running time 150 s / 90°
• Sound power level Max. 35 dB (A)
• Position indication Mechanical, pluggable
• Safety Protection class II Totally insulated
• Degree of protection IP54 in any mounting position
• EMC CE according to 89/336/EEC
• Low voltage directive CE according to 73/23/EEC
• Mode of operation Type 1 (to EN 60730-1)
• Rated impulse voltage 4 kV (to EN 60730-1)
• Control Pollution Degree 3 (to EN 60730-1)
• Ambient temperature range –30 ... +50°C
• Non-operating temperature –40 ... +80°C
• Ambient humidity range 95% r.H., non-condensating (EN 60730-1)
• Maintenance Maintenance-free
• Dimensions / Weight Dimensions See «Dimensions» on page 2
• Weight Approx. 700 g