SKU
LH24A100

LH24A100 - Belimo Linear actuator with rack 150 N, 150 s / 100 mm / constant, AC / DC 24 V

£120.12 £100.10
On request
Next Supplier Stock Update: 18/04/2026
Free delivery over £30
Manuals & Datasheets
 DATA-SHEET 
DATASHEET
 
Product typeActuator
IP ratingIP54
Input SignalOn/Off
ManufacturerBelimo
Power Supply24Vac/Vdc
Torque150 N
Running time140 to 150 sec
Actuator typeLinear

At IACS we provide Free Delivery and Next 1-2 day Delivery for all the Belimo Actuators in stock.

The Belimo LH24A100 is an Actuator used in HVAC applications and air ventilation systems.

The Torque force applied by the LH24A100 is 150 N.

The power supply requested for this Rotary Actuator is 24Vac/Vdc.

IACS has the best prices on the right Belimo Actuators for your system.

Consult the Belimo custom datasheet above or contact iacs via email for personalised assistance if you have queries about size or installation.

LH24A100 - Linear actuator with rack 150 N, 150 s / 100 mm / constant,  AC / DC 24 V

•   Open/Close, 3-point
•   Stroke range 0...100 mm
•   IP 54, Manual override by means of push-button
•   Control with single- / 2-wire contact
•   Connection PVC cable 1m

Features

  • Manual override Manual operation is possible with the pushbutton (the gearing latch remains disengaged as long as the pushbutton is pressed or detented).

  • Stroke adjustment The stroke of the gear rack can be adjusted on both sides in increments of 20 mm by means of mechanical end stops.

  • High functional reliability The actuator is overload-proof, requires no limit switches and automatically stops when the end stop is reached.

•    Electrical data Nominal voltage AC 100 ... 240 V, 50/60 Hz
•    Power supply range AC/DC 19.2 ... 28.8 V
•    Power consumption In operation 1.5 W @ nominal force At rest 0.5 W For wire sizing 3 VA
•    Connection Power supply Cable 1 m, 3 x 0.75 mm2
•    Functional data Actuating force 150 N @ nominal voltage
•   Stroke See «Overview of types»
•   Direction of stroke Reversible with switch 1 resp. 0
•   Running time LH24A60 90 s / 60 mm
•   LH24A100/200/300 150 s / 100 mm
•   Sound power level <35 dB (A)
•   Safety Protection class III Safety extra-low voltage
•   Degree of protection IP54 in any mounting position
•   EMC CE according to 89/336/EEC
•   Mode of operation Type 1 (to EN 60730-1)
•   Rated impulse voltage 0.8 kV (to EN 60730-1)
•   Control pollution degree 3 (to EN 60730-1)
•   Ambient temperature range –30 ... +50°C
•   Non-operating temperature –40 ... +80°C
•   Ambient humidity range 95% r.H., non-condensating (to EN 60730-1)
•   Maintenance Maintenance-free
•   Dimensions / Weight Dimensions See «Dimensions» on page 3
•   Weight See «Overview of types»