SKU
FM150F-SZ

FM150F-SZ - Belimo Flow sensor, AC/DC 24 V, DN 150, FS 54.0 l/s

£1,014.72 £845.60
On request
Next Supplier Stock Update: 18/04/2026
Free delivery over £30
Manuals & Datasheets
 DATA-SHEET 
DATASHEET
 
Product typeSensors & Stats
IP ratingIP54
Output Signal0..10Vdc
ManufacturerBelimo
Power Supply24Vac/Vdc
Sensor TypeFlow Volume Sensor

Find every component of your Air Handling system at IACS. Flow Sensors manufactured by Belimo that are now on hand can all be supplied with either Free or 1-2 Days Delivery.

The Belimo FM150F-SZ is a Sensor that monitors Flows in HVAC applications.

This Sensor is able to utilised in closed systems for both cold and warm water and is resistant to magnetite and dirt.

The ideal Belimo accessories for your system are most affordable at IACS.

If you have questions concerning size or installation, refer to the Belimo custom datasheet above or email IACS for individual ised support.

Electrical data Nominal voltage AC/DC 24 V
  Nominal voltage frequency 50/60 Hz
  Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V
  Power consumption AC 1 VA
  Power consumption DC 0.5 W
  Connection supply Cable 1 m, 3 x 0.75 mm²
 Functional data Application Water
  Voltage output 1x 0...10 V, max. load 1 mA
  Pipe connection Flange PN 16 according to EN 1092-2
  Installation position upright to horizontal
  Servicing maintenance-free
Measuring data Measured values Flow
  Measuring fluid Water and water glycol mixtures
  Measuring principle Ultrasonic volumetric flow measurement
  Measuring accuracy flow ±2% of the measured value (20...100% FS) @
20°C / Glycol 0% vol.
±0.4% of FS (0...20% FS) @ 20°C / Glycol 0% vol.
  Measuring accuracy flow note ±6% of the measured value (20...100% FS) @
-20...120°C / Glycol 0...50% vol.
±1.2% of FS (0...20% FS) @ -20...120°C / Glycol
0...50% vol
  Flow Measurement Repeatability ±0.5%
  Min. flow measurement 1% of FS
Materials Flow measuring pipe EN-GJL-250 (GG 25), with protective paint
Safety data Ambient humidity Max. 95% RH, non-condensing
  Ambient temperature 30...50°C [-22...122°F]
  Fluid temperature -20...120°C [-5...250°F]
  Storage temperature -40...80°C [-40...176°F]
  Protection class IEC/EN III, Safety Extra-Low Voltage (SELV)
  Power source UL Class 2 Supply
  Certification IEC/EN IEC/EN 60730-1:11 and IEC/EN 60730-2-15:10
  Degree of protection IEC/EN IP54
  Degree of protection NEMA/UL NEMA 2
  Enclosure UL Enclosure Type 2
  EMC CE according to 2014/30/EU
  Quality Standard ISO 9001
  Mode of operation Type 1
  Pollution degree 3
  Rated impulse voltage supply 0.8 kV

Mode of operation

The ultrasonic flow sensor is equipped with a flow pipe, four flow transmitters and an electronic circuit. A temperature sensor is mounted in the flow pipe to compensate the temperature effects. A sensor error occurs when the ultrasonic path is interrupted (air bubbles in the system, connection to ultrasonic transducers interrupted).