SKU
FM125F-SZ

FM125F-SZ - Belimo Flow sensor, AC/DC 24 V, DN 125, FS 37.5 l/s

£943.32 £786.10
On request
Next Supplier Stock Update: 18/04/2026
Free delivery over £30
Manuals & Datasheets
 DATA-SHEET 
DATASHEET
 
Product typeSensors & Stats
IP ratingIP54
ManufacturerBelimo
Power Supply24Vac/Vdc
Sensor TypeFlow Volume Sensor

Explore all the components for your ventilation system at IACS. All Belimo Flow Sensors in stock are ready for delivery with either Free or 1-2 Days Delivery.

The Belimo FM125F-SZ is a Sensor used in HVAC applications to track Flow.

With its resistance to magnetite and dirt, this Sensor can be used in closed systems with both cold and warm water.

Find the best-priced Belimo part that is compatible with your system at IACS.

If you have questions about size or installation, consult the Belimo custom datasheet above or send an email to IACS to get personal ised guidance.

Description Show / Hide EditorInsert Image...
Electrical data Nominal voltage AC/DC 24 V
Nominal voltage frequency 50/60 Hz
Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V
Power consumption AC 1 VA
Power consumption DC 0.5 W
Connection supply Cable 1 m, 3 x 0.75 mm²
Functional data Application Water
Voltage output 1x 0...10 V, max. load 1 mA
Pipe connection Flange PN 16 according to EN 1092-2
Installation position upright to horizontal
Servicing maintenance-free
Measuring data Measured values Flow
Measuring fluid Water and water glycol mixtures
Measuring principle Ultrasonic volumetric flow measurement
Measuring accuracy flow ±2% of the measured value (20...100% FS) @
20°C / Glycol 0% vol.
±0.4% of FS (0...20% FS) @ 20°C / Glycol 0% vol.
Measuring accuracy flow note ±6% of the measured value (20...100% FS) @
-20...120°C / Glycol 0...50% vol.
±1.2% of FS (0...20% FS) @ -20...120°C / Glycol
0...50% vol
Flow Measurement Repeatability ±0.5%
Min. flow measurement 1% of FS
Materials Flow measuring pipe EN-GJL-250 (GG 25), with protective paint
Safety data Ambient humidity Max. 95% RH, non-condensing
Ambient temperature 30...50°C [-22...122°F]
Fluid temperature -20...120°C [-5...250°F]
Storage temperature -40...80°C [-40...176°F]
Protection class IEC/EN III, Safety Extra-Low Voltage (SELV)
Power source UL Class 2 Supply
Certification IEC/EN IEC/EN 60730-1:11 and IEC/EN 60730-2-15:10
Degree of protection IEC/EN IP54
Degree of protection NEMA/UL NEMA 2
Enclosure UL Enclosure Type 2
EMC CE according to 2014/30/EU
Quality Standard ISO 9001
Mode of operation Type 1
Pollution degree 3
Rated impulse voltage supply 0.8 kV
Short Description Show / Hide EditorInsert Image...

FM150F-SZ

Ultrasonic Flow Meter

DN 150

Output signal active volumetric flow 54.0

0.5...10 V

Mode of operation

The ultrasonic flow sensor is equipped with a flow pipe, four flow transmitters and an electronic circuit. A temperature sensor is mounted in the flow pipe to compensate the temperature effects. A sensor error occurs when the ultrasonic path is interrupted (air bubbles in the system, connection to ultrasonic transducers interrupted).