SKU
EVC24A-MF-RE

EVC24A-MF-RE Globe Valve Actuator, AC/DC 24 V, 35 s - Belimo | ideal for globe valves

£1,055.04 £879.20
On request
Next Supplier Stock Update: 18/04/2026
Free delivery over £30
Manuals & Datasheets
 DATASHEET 
DATASHEET
 
Product typeActuator
IP ratingIP54
Input Signal0..10 Vdc, MFT, Proportional/MFT
ManufacturerBelimo
Power Supply24Vac/Vdc
Torque2500 N
Running time30 to 45 sec
Ideal for globe valves

For any Belimo Actuators that are in stock at iacs, we offer Free Delivery and Next 1-2 Day Delivery.

The Belimo EVC24A-MF-REis a kind of Actuator used to operate valves in HVAC applications and systems.

The force applied by the Torque of the EVC24A-MF-RE is 2500 N.

This Valve Actuator needs to be supported by a power supply of 24Vac/Vdc.

This Belimo component can be used with Globe Valves.

The ideal Belimo Actuators for your system are most affordable at iacs.

If you have questions concerning size or installation, refer to the Belimo custom datasheet above or email iacs for individualised support.

EVC24A-MF-RE Globe Valve Actuator, AC/DC 24 V, 35 s

  • Globe valve actuator retrofit
  • 2500 N, 50 mm
  • AC/DC 24 V, modulating, multifunctional
  • Actuating time motor 35 s / 40 mm
  • Operating range DC 2...10 V, adj.
  • Position feedback DC 2...10 V, adj.
  • IP54, manual override temporary, perm.
  • Universal valve adapter enclosed
  • Connection cable PVC 1 m

Mode of operation: The actuator is connected with a standard modulating signal of DC 0 ... 10V and travels to the position defined by the positioning signal. The measuring voltage U serves for the electrical display of the actuator position 0 ... 100% and as slave control signal for other actuators.

Parameterisable actuators: The factory settings cover the most common applications. Input and output signals and other parameters can be altered with the PC-Tool MFT-P or with the Service tool ZTH EU.

Installation on third-party valves: The retrofit actuators for installation on a wide range of valves from various manufacturers are comprised of an actuator, universal valve neck adapter and universal valve stem adapter. Adapt the valve neck and valve stem to begin with, then attach the retrofit actuator to the valve neck adapter, connect to the valve and start up. The valve neck adapter/actuator can be rotated through 360° on the valve neck, provided it is permitted by the size of the installed valve.

Installation on BELIMO valves: Please use standard actuators from Belimo for installation on Belimo globe valves. The installation of retrofit actuators on Belimo globe valves is technically possible.

Manual override: Manual override with push-button possible (the gear is disengaged for as long as the button is pressed or remains locked). The stroke can be adjusted by using a hexagon socket screw key (5 mm), which is inserted into the top of the actuator. The stroke spindle extends when the key is rotated clockwise.

High functional reliability: The actuator is overload protected, requires no limit switches and automatically stops when the end stop is reached.

Position indication: The stroke is indicated mechanically on the bracket with tabs. The stroke range adjusts itself automatically during operation.

Home position: Factory setting: Actuator spindle is retracted. The first time the supply voltage is switched on, i.e. at the time of commissioning, the actuator carries out an adaption, which is when the operating range and position feedback adjust themselves to the mechanical setting range. The actuator then moves into the position defined by the positioning signal.

Direction of stroke switch: When actuated, the direction of stroke switch changes the running direction in normal operation.

Adaption and synchronisation: An adaption can be triggered manually by pressing the „Adaption“ button or with the PC-Tool. Both mechanical end stops are detected during the adaption (entire setting range). Automatic synchronisation after pressing the gearbox disengagement button is configured. The synchronisation is in the home position (0%). The actuator then moves into the position defined by the positioning signal. A range of settings can be adapted using the PC-Tool (see MFT-P documentation)

Electrical data:

  • Nominal voltage AC/DC 24 V
  • Nominal voltage frequency 50/60 Hz
  • Nominal voltage range AC 19.2...28.8 V / DC 21.6...28.8 V
  • Power consumption in operation 11 W
  • Power consumption in rest position 1.5 W
  • Power consumption for wire sizing 18 VA
  • Connection supply / control Cable 1 m, 4 x 0.75 mm²
  • Parallel operation Yes (note the performance data)

Functional data:

  • Actuating force 2500 N
  • Positioning signal Y DC 0...10 V
  • Positioning signal Y note Input impedance 100 kΩ
  • Control signal Y variable Open-close, 3-point (AC only) and Modulating (DC 0...32 V)
  • Operating range Y DC 2...10 V
  • Operating range Y variable Start point DC 0.5...30 V and End point DC 2.5...32 V
  • Position feedback U DC 2...10 V
  • Position feedback U note Max. 0.5 mA
  • Position feedback U variable Start point DC 0.5...8 V and End point DC 2.5...10 V
  • Position accuracy 5% absolute
  • Manual override Gear disengagement with push-button, can be locked
  • Nominal stroke 50 mm
  • Actuating time 35 s / 40 mm (44 s / 50 mm)
  • Actuating time variable 44...113 s / 50 mm
  • Adaption setting range manual (automatic on first power-up)
  • Adaption setting range variable No action, adaption when switched on, adaption after pushing the gear disengagement 
  • Override control MAX (maximum position) = 100%, MIN (minimum position) = 0% and ZS (intermediate position, AC only) = 50%
  • Override control variable MAX = (MIN + 33%)...100%, MIN = 0%...(MAX – 33%) and ZS = MIN...MAX
  • Sound power level motor 65 dB(A)
  • Position indication Mechanically, 5...50 mm stroke

Safety:

  • Protection class IEC/EN III Safety extra-low voltage
  • Degree of protection IEC/EN IP54
  • EMC CE according to 2004/108/EC
  • Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14
  • Mode of operation Type 1
  • Rated impulse voltage supply / control 0.8 kV
  • Control pollution degree 3
  • Ambient temperature 0...50°C
  • Non-operating temperature -40...80°C