| Product type | Sensors & Stats |
| IP rating | IP65 |
| Output Signal | 0..10Vdc |
| Manufacturer | Carel |
| Sensor Type | Air Quality |
| Sensor characteristics | Duct Mounted |
|
TECHNICAL FEATURES - ACTIVE AIR QUALITY SENSORS DUCT VERSION |
|
|
|
|
|
DPDQ306000 (VOC) |
|
|
Sensor: |
VOC sensor
(metal oxide) |
|
Measuring range: |
0…100%
air quality; referred to calibrating gas |
|
Output signal: |
0-10 V (0
V=clean air, 10 V=polluted air) o 4…20 mA
(selectable via jumper) |
|
Measuring accurancy: |
±
20% of final value (referred to calibrating gas) |
|
Long-term stability: |
<10% /
per year |
|
Sensor protection: |
sinter
filter, exchangeable, screwed, easy to clean |
|
DPDQ402000 (CO2) |
|
|
Sensor CO2: |
optical
sensor |
|
Measuring CO2: |
0…2000
ppm CO2 |
|
Output CO2: |
0-10 v |
|
Measuring accurancy CO2: |
± 30
ppm, ± 5% of final value |
|
Long-term stability: |
+ 1% of
final value per year |
|
|
|
|
DPDQ502000 (VOC+CO2) |
|
|
Air quality sensor: |
VOC sensor
(metal oxide) |
|
Measuring range, air quality |
0…100%
(mixed gas pollution referred to calibrating gas) |
|
Output air quality: |
0-10 V (0
V=clean air, 10 V=polluted air) |
|
Measuring accuracy, air quality: |
±
20% of final value (referrred to calibrating gas) |
|
|
|
|
Common features |
|
|
Power supply: |
24
Vac/15-36 Vdc |
|
Ambient temperature: |
0…+50
°C |
|
Electrical connection: |
0.14
– 1.5 mm2 via screw terminals on circuit board |
|
Warm-up period: |
1 hour |
|
Installation: |
by mounting
flange, plastic and galvanised steel optional |
|
Protection type: |
IP65
(according to IEC 529) |