Mode of operation: The ball valve is operated by a rotary actuator. The rotary actuator is controlled by an open-close signal or by a standard modulating or 3-point control system and moves the ball of the valve – the throttling device – to the position dictated by the control signal. Open the ball valve counterclockwise and close it clockwise.
Simple direct mounting: Tool-free snap assembly. The actuator can be plugged on the valve by hand (Caution! Just vertical movements). Pins must match the holes on the flange. The mounting orientation in relation to the valve can be selected in 180° increments. (Possible two times)
Functional data:
Media Cold and warm water, water with glycol up to max. 50% vol.
Medium temperature 2...90°C
Permissible pressure ps 1600 kPa
Closing pressure ∆ps 350 kPa
Differential pressure ∆pmax 280 kPa
Differential pressure note 50 kPa for low-noise operation
Flow characteristic equal percentage, optimised in the opening range
Leakage rate Leakage rate A, tight (EN 12266-1)
Flow setting see Installation instructions
Pipe connector Internal thread according to ISO 7-1
Angle of rotation 90° (Operating range 15...90°)
Installation position Upright to horizontal (in relation to the stem)