AX-RLA-DC - Raise/Lower to Analogue Module 24Vdc Features:
Supply voltage 24Vac or 24Vdc (+/-15%)
Supply current 30 mA DC / 60 mA AC (Not including input current)
Inputs 12 to 24 Vac/dc or volt free Raise and Lower signals
Input load Approximately 10mA at 24Vac with J1 or J2 in N position
Approximately 50mA at 24Vac with J1 or J2 in T position
Raise Lower timing 30 to 300 seconds, see table
Outputs 0 - 10Vdc at 10mA maximum load; 24V supply feed through
Terminals Rising clamp for 0.5-2.5mm2 cable
Ambient temperature range 0°C to 50°C
Dimensions 45(W) x 83(H) x 45(D) mm (Maximum)
Weight 50 grams
Country of origin United Kingdom
AX-RLA-DC - Raise/Lower to Analogue Module 24Vdc :
The Axio AX-RLA isolates and converts a raise-lowerinput signal into a 0-10 volt analogue output. The unitprovides sixteen raise-lower cycle times and a manualoutput override for commissioning. The input commoncan be connected to the signal 0V or supply voltageallowing the inputs to be voltages (AC/DC) or switchingsignals. Input load resistors can be selected for triacswitching. The unit also provides a 24V supply feedthrough for valve actuators, etc. to simplify cabling. TheAX-RLA is supplied in a DIN rail carrier suitable formounting on TS35 section DIN rail and features highquality rising clamp terminals for ease of connection.
Input Signal: 0-10V dc (1mA max)
Output Contacts: 2 x SPCO
Contact Rating: 12A @ 250V ac (res.)
Power Supply: 24V ac or dc
Supply current: 50 mA dc / 125 mA ac maximum
Power Consumption: 70mA max@24V ac, 50mA max@24Vdc
Modes of Operation: Cycle Times: ARL, ARL
Variable 1: 90 to 300 secs, 10 to 30 secs
Fixed: 210 secs, 90 secs
Variable 2: 30 to 150 secs, 60 to 120 secs
Manual Override: ON/OFF/AUTO (Link Selectable)
Reset: Automatic 24 hour reset for 115% of range
Terminals: Rising Clamp for 0.5-2.5mm2Cable
LED Indicators: ON when relay energised
Ambient Range: 0 to 50°C
Dimensions: 83mm (l) x 46mm (w) x 45mm (h) (approx.)