The Axio AX-RHT-3-x range of RH & T Transmitters provide accurate Relative Humidity and Temperature measurements, with selectable current or voltage analogue outputs. The units are extremely reliable, have excellent stability and a quick response time. The standard accuracy range is 3%.
RH accuracy +/- 3% typical
Temperature accuracy +/- 0.3°C typical
Sensor type Capacitive
Sensor protection PTFE filter
Long term stability +/-1% RH at 50% RH in 5 years
Repeatability +/- 0.5% RH
Hysteresis +/-1% of span max
Response time 15 seconds @ 25°C, but dependant on airflow
Supply voltage 24Vac/dc (+/-15%) (24Vdc only for Room unit with 4-20mA output selected)
Output (voltage) 0 – 10Vdc or 0 – 5Vdc at 10mA maximum load
Output (current) 4-20mA at 500Ohms maximum load
Output range - Relative Humidity 0 to 95%
Output range - Temperature Room -10°C to +40°C, Duct 0°C to +70°C, Outside Air -20°C to +50°C
Terminals Rising clamp for 0.5-2.5mm2 cable
Ambient temperature range -10°C to 50°C, 0-95% RH
Dimensions, weight & protection:
● Room: 85 x 85 x 24mm, 75g, IP20 ● Duct: 115 x 80 x 52mm housing - 230(L) x 12mm ∅ maximum probe, 115g, IP65 (housing only) ● Outside air: 115 x 80 x 52mm, 140g, IP65 (housing only)