AX-DIM6-MI-I - Six channel Multiplexer, current output Features:
6 x VFC or 24Vac/dc inputs
Voltage and Current Output Variants
DIN Rail Mounting
Operates From 24V ac or dc Power Supply
LED Input Status Indication
Input Simulation
AX-DIM6-MI-I - Six channel Multiplexer, current output:
The AX-DIM6-MI multiplexes 6 VF. or 24Vac/dc signals into a single analogue output. 0-10Vdc, 2-10Vdc or 4-20mA, and 0-20mA output variants are available making the unit compatible with a large range of BMS equipment. The input registers as active when the contact is closed. Additionally, jumpers are fitted to allow each input to be manually overriden for commissioning and testing purposes. The output sequence can also be reversed as required by some types of controller and control strategies.
Inputs: 6 x Volt free contacts or 24Vac/dc input signals
Output Voltage: 0 - 10Vdc at maximum load 10mA. (2-10Vdc link selectable)
Output Current: 4 to 20mA (link selectable 0-20mA), max resistance of load 500 Ω
LED Indication: ON when Input is ON
Power Supply: 24V ac or dc (+/-15%)
Power Consumption: 24Vdc 40mA max, 24V ac 60mA max