| Product type | Sensors & Stats |
| IP rating | IP55 |
| Output Signal | 0..1 Vdc, 4..20 mA |
| Manufacturer | Carel |
| Sensor Type | Temperature |
| Sensor characteristics | Flying Lead, Immersion |
|
TECHNICAL FEATURES |
|
|
|
|
|
Power supply |
9 to 30 Vdc or
12 to 24 Vac (-10% to +15%), 50/60 Hz |
|
Operating conditions |
-10T70 °C, <90% rH
non-condensing |
|
Storage conditions |
-20T70 °C, <90% rH
non-condensing |
|
Range |
-30T90 °C |
|
Precision |
25 °C: ±0.5 °C; -30T90 °C: ±1 °C |
|
Output signals |
-0.3 to 1 V; 4 to 20 mA |
|
Time constants |
200 s (still air); 45 s (3 m/s) |
|
Index of protection |
IP55 (case); IP67 (sensor) |